Performance Analysis of Underground Duct for room environment control

dc.contributor.authorSingh, Pawanjot
dc.contributor.supervisorSharma, Sumeet
dc.contributor.supervisorJindal, T. K.
dc.date.accessioned2013-09-20T11:52:55Z
dc.date.available2013-09-20T11:52:55Z
dc.date.issued2013-09-20T11:52:55Z
dc.descriptionME, MEDen
dc.description.abstractEarth-pipe-air heat exchanger systems can be used to reduce the cooling load of buildings in summer. In a developing country like India, there is a huge gap in demand and supply of electricity and rising electricity prices have forced us to look for cheaper and cleaner alternative. Our objective can be met by the use of ground heat exchangers and the system is very simple which works by moving the heat from the house into the earth during hot weather. Measurements show that the ground temperature below a certain depth remains relatively constant throughout the year. Experimental investigations were done on the experimental set up in PEC University of Technology, Chandigarh. Effects of the operating parameters i.e air velocity and temperature on the thermal performance of horizontal ground heat exchanger are studied. For the pipe of 13.6 m length and 0.15 m diameter, temperature rise of 5.90C-11.90C have been observed for the outlet flow velocity ranging from 1.8m/s to 4.1 m/s. At higher outlet velocity and maximum temperature difference, the system is most efficient to be used.en
dc.format.extent2743377 bytes
dc.format.mimetypeapplication/pdf
dc.identifier.urihttp://hdl.handle.net/10266/2509
dc.language.isoenen
dc.subjectUnderground duct, heat exchangeren
dc.titlePerformance Analysis of Underground Duct for room environment controlen
dc.typeThesisen

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
2509.pdf
Size:
2.62 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.79 KB
Format:
Item-specific license agreed upon to submission
Description: