Enhancement of Maximum Loading For Radial Distribution Network
Loading...
Files
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
In this Thesis work, an attempt has been made for reconfiguration of electric
power distribution system. A new formula for computing the reconfiguration of
any distribution network is proposed in this thesis work. The node having the
minimum value of voltage deviation w.r.t pu value is the most sensitive node.
Using example of 69-node radial distribution networks, it has been shown that
the node having the minimum value of voltage deviation w.r.t pu value become
most sensitive node using the proposed method which is also the end node. The
critical values of total real power load (TPL) and total reactive power load
(TQL) for constant power are derived out for the sub-station voltage of 1.0 pu.
for 69-node radial distribution network. The proposed method will reduce the
real and reactive power losses, improves voltage profile and enhances the
loading capability of distribution network.
The voltage deviation is reduced to 6% from 10%.The superiority of the
proposed method has been established by taking results iteratively and
comparing with other literatures.
Description
M.E. (Power Systems and Electric Drives)