The nonlinear loads causes harmonic pollution in electrical power system. These harmonics or harmonic components affect the performance of power system components as well as the com- ponents causing harmonics. The line admittances get modified to unacceptable limits which thereby results in error during fundamental load flow calculations. In this dissertation, an ef- ficient methodology to determine the harmonic sources and their injection levels has been im- plemented. The measurement data of phasor measurement units (PMUs) are considered as the time synchronised voltage and current phasor values of buses. Because of high cost associ- ated with PMUs, optimal placement of PMUs has been investigated with index method, genetic method and binary particle swarm optimization approaches. The harmonic identification ap- proach utilizes the direction of harmonic power flow at system buses. The effectiveness of the formulations is studied on 18-bus and 69-bus radial distribution systems and compared. The simulation is implemented in MATLAB.